Cu-BV-H07V-U-450-750V
H07V-U(BV)is used for laying in electric - installation tubes, under and on plaster installation in dry rooms and in closed installation conduits. Direct laying in cable guides is not permitted. Also applied for internal wiring of distribution and switching boxes equipment.
key word:
Building Wire H07-U 450-750V
Category:
Product Description
Building Wire-Cu-H07-U 450-750V
Application
H07V-U(BV)is used for laying in electric - installation tubes, under and on plaster installation in dry rooms and in closed installation conduits. Direct laying in cable guides is not permitted. Also applied for internal wiring of distribution and switching boxes equipment.
Construction
Conductor: Copper, class 1, solid conductors
Insulation: PVC
Specification
IEC 60228 Conductors of Insulated Cables
IEC 60227-3 Polyvinyl Chloride Insulated Cables of Rated Voltages up to and Including 450/750 V – Part 3: Non-sheathed Cables for Fixed Wiring
DIN VED 0281-3 Polyvinyl Chloride Insulated Cables of Rated Voltages up to and Including 450/750 V – Part 3: Non-sheathed Cables for Fixed Wiring
Characteristics
Rated voltage Uo/U: 450/750 V;
Normal operating temperature: 70˚C.
Short circuit temperature (5 seconds maximum duration): 160˚C.
IEC 60227-3 (mark 60227 IEC 01)
Minimum bending radius:
4D for D < 8mm
5D for 8mm < D < 12mm Note: D is overall diameter of cable.
6D for D > 12mm
H07V-U (BV)
| Conductor | Insulation Thickness | Overall Diameter | Approx. Weight | Max. D.C. Resistance of Conductor at 20℃ | Allowable Ampacities | ||
| Min. | Max. | ||||||
| mm2 | Class of Conductor | mm | mm | mm | kg/km | Ω/km | A |
| 1.5 | 1 | 0.7 | 2.6 | 3.2 | 21 | 12.1 | 18 |
| 2.5 | 1 | 0.8 | 3.2 | 3.9 | 32 | 7.41 | 25 |
| 4 | 1 | 0.8 | 3.6 | 4.4 | 47 | 4.61 | 33 |
| 6 | 1 | 0.8 | 4.1 | 5 | 65 | 3.08 | 42 |
| 10 | 1 | 1 | 5.3 | 6.4 | 110 | 1.83 | 58 |