榆次Cu-RV-H07V-K 450-750V

H07V-K (RV) is used for laying in electric - installation tubes, under and on plaster installation in dry rooms and in closed installation conduits. Direct laying in cable guides is not permitted. Also applied for internal wiring of distribution and switching boxes equipment.

产品描述

Building Wire-Cu-H07-K 450-750V

Application

H07V-K (RV) is used for laying in electric - installation tubes, under and on plaster installation in dry rooms and in closed installation conduits. Direct laying in cable guides is not permitted. Also applied for internal wiring of distribution and switching boxes equipment.

Construction

Conductor: Copper, class 5, solid conductors 
Insulation: PVC

Specification

IEC 60228 Conductors of Insulated Cables
IEC 60227-3 Polyvinyl Chloride Insulated Cables of Rated Voltages up to and Including 450/750 V – Part 3: Non-sheathed Cables for Fixed Wiring
DIN VED 0281-3 Polyvinyl Chloride Insulated Cables of Rated Voltages up to and Including 450/750 V – Part 3: Non-sheathed Cables for Fixed Wiring

Characteristics

Rated voltage Uo/U: 450/750 V;
Normal operating temperature: 70˚C.
Short circuit temperature (5 seconds maximum duration): 160˚C.
IEC 60227-3 (mark 60227 IEC 01)
Minimum bending radius:
4D for D < 8mm
5D for 8mm < D < 12mm
6D for D > 12mm
Note: D is overall diameter of cable.
 

H07V-K (RV)

Conductor Insulation Thickness Overall Diameter Approx. Weight Max. D.C. Resistance of Conductor at 20℃ Allowable Ampacities
Min. Max.
mm2 Class of Conductor mm mm mm kg/km Ω/km A
1.5 5 0.7 2.8 3.4 21 13.3 18
2.5 5 0.8 3.4 4.1 34 7.98 25
4 5 0.8 3.9 4.8 50 4.95 33
6 5 0.8 4.4 5.3 71 3.3 42
10 5 1 5.7 6.8 107 1.91 58
16 5 1 6.7 8.1 169 1.21 78
25 5 1.2 8.4 10.2 266 0.78 105
35 5 1.2 9.7 11.7 347 0.554 130
50 5 1.4 11.5 13.9 486 0.386 155
70 5 1.4 13.2 16 705 0.272 200
95 5 1.6 15.1 18.2 905 0.206 250
120 5 1.6 16.7 20.2 1117 0.161 290
150 5 1.8 18.6 22.5 1380 0.129 335
185 5 2 20.6 24.9 1742 0.106 390
240 5 2.2 23.5 28.4 2152 0.0801 470